Impact of Short-Term Power Shortage from Low Voltage Ride through and DC Commutation Failure on Power Grid Frequency Stability

Wenjia Zhang*, Sixuan Xu, Wanchun Qi, Zhuyi Peng, Wentao Sun

Institute of Economics and Technology, State Grid Jiangsu Electric Power Co., Ltd., Nanjing, 610095, China

* Corresponding Author: Wenjia Zhang. Email: email

Energy Engineering 2025, 122(6), 2371-2387. https://doi.org/10.32604/ee.2025.064160

Abstract

Countries worldwide are advocating for energy transition initiatives to promote the construction of low-carbon energy systems. The low voltage ride through (LVRT) characteristics of renewable energy units and commutation failures in line commutated converter high voltage direct current (LCC-HVDC) systems at the receiving end leads to short-term power shortage (STPS), which differs from traditional frequency stability issues. STPS occurs during the generator’s power angle swing phase, before the governor responds, and is on a timescale that is not related to primary frequency regulation. This paper addresses these challenges by examining the impact of LVRT on voltage stability, developing a frequency response model to analyze the mechanism of frequency instability caused by STPS, deriving the impact of STPS on the maximum frequency deviation, and introducing an energy deficiency factor to assess its impact on regional frequency stability. The East China Power Grid is used as a case study, where the energy deficiency factor is calculated to validate the proposed mechanism. STPS is mainly compensated by the rotor kinetic energy of the generators in this region, with minimal impact on other regions. It is concluded that the energy deficiency factor provides an effective explanation for the spatial distribution of the impact of STPS on system frequency.

Keywords

Commutation failure; frequency stability; LVRT; renewable energy; short-term power shortage; LCC-HVDC

Cite This Article

APA Style
Zhang, W., Xu, S., Qi, W., Peng, Z., Sun, W. (2025). Impact of Short-Term Power Shortage from Low Voltage Ride through and DC Commutation Failure on Power Grid Frequency Stability. Energy Engineering, 122(6), 2371–2387. https://doi.org/10.32604/ee.2025.064160
Vancouver Style
Zhang W, Xu S, Qi W, Peng Z, Sun W. Impact of Short-Term Power Shortage from Low Voltage Ride through and DC Commutation Failure on Power Grid Frequency Stability. Energ Eng. 2025;122(6):2371–2387. https://doi.org/10.32604/ee.2025.064160
IEEE Style
W. Zhang, S. Xu, W. Qi, Z. Peng, and W. Sun, “Impact of Short-Term Power Shortage from Low Voltage Ride through and DC Commutation Failure on Power Grid Frequency Stability,” Energ. Eng., vol. 122, no. 6, pp. 2371–2387, 2025. https://doi.org/10.32604/ee.2025.064160



cc Copyright © 2025 The Author(s). Published by Tech Science Press.
This work is licensed under a Creative Commons Attribution 4.0 International License , which permits unrestricted use, distribution, and reproduction in any medium, provided the original work is properly cited.
  • 382

    View

  • 209

    Download

  • 0

    Like

Share Link