A Novel Control-Protection Coordination Strategy of Power Lines Connected with Inverter-Based Resources
1 College of Engineering, Beijing Forestry University, Beijing, China
2 Tianshui Power Supply Company, State Grid Gansu Electric Power Company, Tianshui, China
3 Jinhua Power Supply Company, State Grid Zhejiang Electric Power Company, Jinhua, China
* Corresponding Author: Sumei Liu. Email:
Energy Engineering 2026, 123(6), 2 https://doi.org/10.32604/ee.2026.081082
Received 23 February 2026; Accepted 02 April 2026; Issue published 27 May 2026
Abstract
The unique fault current characteristics of inverter-based resources (IBRs) result in a variable angle of the additional impedance for conventional distance protection, causing failure to operate for internal faults and maloperation for external faults. To address this issue, a novel control-protection coordinated strategy is proposed. The positive-sequence current references of IBRs’ inverter control strategy are reset, based on the relationship between the current on the high-voltage side of the transformer and that of the fault-point current. Under such control, the additional impedance angle can be effectively maintained at a constant value. On this basis, a single-ended protection principle immune to the additional impedance is developed. The proposed control-protection coordinated strategy can effectively identify internal and external faults under high-penetration IBRs integration, without substantially modifying the existing inverter control and protection framework. Compared with existing control-protection coordinated strategies, the proposed improved control strategy will not affect the stability of inverter control, nor will it generate additional harmonics. The proposed protection strategy still adopts conventional power-frequency voltage and current quantities for fault identification, facilitating its implementation.Keywords
With the growing penetration of inverter-based resources (IBRs, e.g., photovoltaics (PV) plants, energy storage (ES), and permanent magnet direct-driven (PMDD) wind farm), the fault current characteristics of the connected grids are fundamentally altered [1–3]. As a result, significant challenges are presented to existing protection strategies, particularly for distance protection. Some typical cases are: (1) The distance protection for a 110 kV line connected with a wind farm in North China maloperated during a reverse external fault [4]; (2) A 110 kV feeder of 220 kV substation in Central China incorrectly operated during external faults due to impedance measurement distortion caused by wind farm integration [5]. Thus, widespread attention is paid to the mis-operation issues in distance protection caused by IBR integration [6–8].
To tackle the aforementioned issues, most studies develop either enhanced protection criteria or novel criteria based on the unique fault features of IBRs. Based on the assumption that the angle of the IBRs’ short-circuit current is consistent with that of the fault-point current, in [9] the measured impedance is recalculated for the adaptive Zone II distance protection principle. Although the protection can eliminate the influence of fault resistance on the measured impedance, its performance is significantly affected by the angle characteristics of fault current from IBRs. In fact, the mentioned angle characteristics are governed by the IBRs’ control strategy. Ref. [10] also develops an adaptive mho characteristic-based distance protection to mitigate the adverse effect of fault resistance caused by the IBRs’ integration. The protection operation zone varies with the additional impedance angle. However, the additional impedance angle is obtained based on the assumption that IBRs do not provide negative-sequence current. Ref. [11] proposes an adaptive distance relay setting based on specific positive and negative sequence impedances of the IBRs. The impedance characteristic depends on the IBRs’ specific control strategy, which adopts a dual-sequence reference frame to mitigate the dc-link oscillation and reduce the negative-sequence voltage. To sum up, the effectiveness of the aforementioned protection strategies is influenced by the IBRs’ fault characteristics. The IBRs’ fault characteristics are various with their control strategies [12].
Different from the previous studies, some control-protection coordination strategies are also adopted. These strategies mainly modify the control strategies to restore fault identification of distance protection, or improve both the control strategies and the distance protection criteria simultaneously. In terms of modifying the control strategies of IBRs, in [13] the positive reference values of current control loops for IBRs are reset to emulate the phase relationship between the positive- and negative-sequence currents supplied by synchronous generators (SGs). This approach can prevent incorrect operation of distance relays for IBR-connected lines, but it is only applicable to asymmetrical faults. In [14], the current references of IBRs are also adjusted so that the measured reactance of the distance relay is mostly equal to the actual line reactance under various fault types. However, the limited amplitude of fault currents from IBRs easily leads to an excessively large resistive component in the measured impedance [15,16], resulting in incorrect operation of the protection during high-resistance faults. In fact, the performance of distance protection is affected by the amplitude relationship between short-circuit currents at both ends of IBR-connected lines [17]. The larger the amplitude difference is, the greater the error between the measured impedance and the actual line impedance becomes. Whereas, the short-circuit current amplitude supplied by IBRs is inherently small (only 1.2–1.5 times the rated current) [18], which results in a high risk of incorrect operation for conventional distance protection.
In terms of developing the protection principles on the basis of improving the IBRs’ control strategies, most studies focus on two-terminal differential protection [19–21]. Nevertheless, the two-terminal protection relies on communication, and it is difficult to implement. Therefore, some single-terminal protection strategies are also studied for IBR-connected lines by modifying inverters’ control strategies. Ref. [22] proposes an improved time-domain distance protection based on adaptive high-frequency voltage control. In order to accurately calculate the fault distance, a 400 Hz negative-sequence voltage signal is modulated via the inverter’s negative-sequence control. However, this study is aimed at an MMC-based offshore AC network. Ref. [23] also proposes an improved time-domain distance protection strategy by injecting a 20 Hz modulated voltage signal into IBRs’ inverter control. However, the continuous injection may cause grid harmonic distortion. And the signals’ characteristics may also be influenced by the power grid topologies, their corresponding parameters, and so on [24]. As a result, it impairs the performance of protection strategies based on these signals.
Different from the mentioned protection strategies based on the characteristic signals, the negative sequence fault current of IBRs is altered by optimizing the inverters’ control strategy in [25] in order to accurately identify the faulty distance. Such approach does not affect the power quality of the grid, but the presence of negative-sequence current can cause inverter control instability due to dc-link voltage fluctuations [26].
As analyzed above, the key issues to be addressed in designing a control-protection coordinated strategy include: (1) The improved control strategy can generate unique electrical quantities suitable for fault identification without compromising the control stability of the inverter; (2) The developed protection principle only requires local electrical quantities, independent of the fault conditions, IBRs’ capacity, and so on. Aimed at these problems, in this manuscript a novel control–protection coordination strategy for transmission lines connected with IBRs is proposed. And its main contributions are summarized as follows:
(1) An enhanced control strategy for the IBRs’ inverters is proposed through resetting positive-sequence current references to ensure that the additional impedance angle is reduced to zero. The adjusted current references do not compromise the inverter control stability.
(2) The proposed protection criterion belongs to single-ended quantity protection, which employs the reactance component of the measured impedance for estimating fault distance. Even under high-penetration IBRs integration scenarios, it can effectively mitigate the impact of fault resistance.
The rest of this paper is organized as follows. Section 2 qualitatively analyzes and reveals the relationship between IBRs’ control strategies and the impedance measurement of distance protection. Section 3 proposes an enhanced control strategy for the IBRs’ inverters and derives analytical expressions of fault-point current angles under different fault types by using only electrical quantity from the IBRs’ side. Section 4 develops a novel single-ended protection criterion. Section 5 verifies the effectiveness of the proposed control strategy and protection criterion using PSCAD/EMTDC simulations.
2 The Challenges of Traditional Distance Protection Applied for the IBRs-Connected Lines
Here the conventional distance protection of the line connected with a photovoltaic (PV) power station is taken as an example to analyze its applicability. The grid-connected system topology of the PV power station is shown in Fig. 1. In Fig. 1, B1 and B2 represent the distance relay at both ends of the 110 kV line MN. And

Figure 1: Grid-connected topology diagram of PV power station.
When the fault f1 with fault resistance Rf occurs in Fig. 1, the measured impedance of distance relay B2 on the PV station side can be expressed as
where
As shown in (1), the difference between measured impedance
The sign of the additional impedance angle

Figure 2: The variation range of the additional impedance angle with the change of the IBRs-side fault current. (a) the PV-side current leading the fault-point current; (b) the PV-side current lagging the fault-point current.
By contrast, as shown in Fig. 2b, when the PV-side fault current lags the fault-point current,
In summary,
3 An Enhanced Control Strategy for the IBRs’ Inverters
From the above analysis, the variation of
3.1 The Relationship between Positive-Sequence Current Reference and Fault-Point Current Angle
The control block diagram of the grid-connected IBRs is shown in Fig. 3. Considering that most inverters adopt a negative-sequence current suppression strategy during faults, in this paper the positive-sequence current references are reset to align the angle of the current

Figure 3: The control block diagram of the grid-connected IBRs.
As the line studied in this paper is the distance protection on the IBRs side of a dedicated IBRs-connected outgoing line, no intermediate taps, load branches or other power sources are connected between the high-voltage side of the grid-connected inverter transformer and bus N. Also, for the 110 kV medium and short-distance line, the distributed capacitive current is extremely small at power frequency, and its influence on the currents at both sides is negligible. Therefore, current continuity is maintained in the line section, and the current amplitude and phase remain consistent. Thus, it is considered that
Further considering the overcurrent capacity limits of IBR inverters
where
3.2 Calculation of the Positive-Sequence Current Reference under Different Fault Types
Considering that the fault-point current
(1) Three-Phase Fault
A three-phase fault is a symmetrical fault, and thus only positive-sequence components are considered. Fig. 4 shows the fault-component equivalent network under a three-phase fault.

Figure 4: The fault component equivalent network under a three-phase fault.
According to Fig. 4, the fault-point current
where
It is assumed that both the grid-side positive-sequence equivalent impedance and the line impedance satisfy
where
(2) Phase to Phase Fault
A phase-to-phase fault is an unsymmetrical fault, and thus the positive-sequence and negative-sequence components should be considered. Fig. 5 shows the fault-component equivalent network under the phase-B-to-phase-C fault.

Figure 5: The fault component equivalent network under a phase-to-phase fault.
According to Fig. 5, the fault-point current under the phase-B-to-phase-C fault can be expressed as
where
From (7), the fault-point current angle can also be calculated based on the electrical quantities
(3) Phase-to-Phase Ground Fault
A double-phase-to-ground fault is an unsymmetrical fault, and thus the positive-sequence, negative-sequence and zero-sequence components are considered. Fig. 6 shows the fault-component equivalent network under the phase B-to-phase C ground fault.

Figure 6: The fault component equivalent network under a phase-to-phase ground fault.
As shown in Fig. 6, the fault-point current under the phase-B-to-phase-C-to-ground fault can be expressed as
In (8),
(4) Single-Phase-to-Ground Fault
A single-phase ground fault is an unsymmetrical fault, and thus the positive-sequence, negative-sequence and zero-sequence components should be considered. Fig. 7 shows the fault-component equivalent network under a phase-A ground fault. Combined with Fig. 7,

Figure 7: The fault component equivalent network under a single-phase-to-ground fault.
From the preceding derivations, the fault-point current angles under different fault types can be calculated based on

As shown in Table 1, the current references for IBRs inverter control can be obtained using the locally measured
It is worth emphasizing that the derivations above strictly rely on the assumption
To evaluate the applicability of the proposed method under these challenging conditions, the simulation studies in Section 5 will further investigate the angle tracking performance and protection behavior under weak grid and high IBR penetration scenarios, thereby demonstrating the robustness and limitations of the proposed strategy.
4 A Novel Single-Ended Protection Strategy
Under the mentioned control strategy, the current angle provided by the IBRs is dynamically altered in order to align the angle of
where RNk is the resistive component of the faulted line’s actual impedance;
Fig. 8 shows the measured impedance characteristics under internal and external faults. As shown in Fig. 8, the measured impedance variation depends on the fault resistance Rf and the current amplitude ratio of

Figure 8: The measured impedance characteristics under internal and external faults.
Under internal faults, the measured impedance increases with rising Rf and the ratio. Its core characteristic is that the resistance component increases while the reactance component of the measured impedance remains constant, which corresponds to the actual reactance of the faulted line’s actual impedance. Under external faults, the measured impedance shows a similar trend to that under internal faults. However, the reactance component of the measured impedance under external faults differs significantly from that under internal faults. Specifically, the reactance component maintains a smaller constant under internal faults and a larger constant under external faults. The reactance component of the measured impedance directly corresponds to the reactance component of the faulted line’s actual impedance and can effectively characterize the actual fault distance. Therefore, based on the difference in the reactance component of the measured impedance between internal and external faults, a single-ended protection principle immune to the additional impedance is developed as follows.
where
Forward internal fault (
Reverse fault (
Forward external fault (
Although the proposed reactance principle accurately locates faults and mitigates the additional impedance interference, the performance can be adversely affected by boundary conditions, IBR fluctuations and system oscillations. To overcome these shortcomings, two auxiliary criteria are proposed to improve protection performance as follows.
Auxiliary Criterion 1: To mitigate the risks of maloperation for the main protection criterion under IBRs output current fluctuations and transient disturbances, A starting criterion using abrupt current changes on the high-voltage side of the transformer and the voltage at grid-connected bus N is proposed in Section 4.2. If the criterion is satisfied, the main protection and identification strategy is activated; otherwise, the protection is blocked.
Auxiliary Criterion 2: To solve the maloperation and poor selectivity of the pure reactance criterion at the protection zone boundary, under high-resistance faults and control-protection coordination failure, a simple resistance threshold criterion is proposed, which can be expressed as:
where
4.2 Flowchart of the Proposed Protection Strategy
The proposed control-protection coordination strategy is implemented through the process illustrated in the Fig. 9. This strategy comprises four main stages: start-up criterion fault phase selection, control strategy switching, fault current calculation, and protection criterion. The detailed analysis is provided as follows.

Figure 9: The control-protection coordination flowchart proposed in this paper.
(1) Evaluate Starting Criteria
To ensure reliable activation of the proposed control-protection coordination scheme while maintaining sensitivity for both metallic and high-resistance faults, a composite starting criterion based on local electrical quantities is developed. The criterion employs an “OR” logic between the undervoltage and overcurrent conditions, as expressed in (14):
where the voltage threshold is set at 0.9 p.u. in accordance with typical low-voltage ride-through standards. The current variation threshold
The proposed protection starting criterion employs the OR logic of undervoltage and overcurrent criteria, which are complementary under various fault conditions. For high-resistance faults with weak voltage drops, the overcurrent criterion can effectively improve the starting sensitivity. In contrast, under weak grid conditions and high IBR penetration scenarios where the fault current is relatively low, the undervoltage criterion guarantees reliable starting. Furthermore, the criterion is identified using electrical data within only 1–2 fundamental frequency cycles, which can not only achieve fast response but also avoid misjudgment caused by normal system disturbances. The combined logic thus ensures high sensitivity and reliability under diverse operating conditions.
Once the starting criterion is satisfied, the adaptive phase control strategy described in Section 3 is immediately activated, and the distance protection element is triggered to enter the fault identification process. Simulation results in Section 5 will verify the effectiveness and reliability of the proposed starting criterion under disturbance scenarios.
(2) Identify Faulted Phase
Rapid and accurate identification of the fault type is the foundation for all subsequent analysis and control. Traditional phase selection elements are predominantly based on the principle of phase current difference variation, whose effectiveness relies on a significant difference in current variation between the faulted phases and the healthy phases. However, constrained by the internal control strategies of inverters, the short-circuit current exhibits characteristics such as limited magnitude and controlled phase. This results in a small magnitude and gradual change in the short-circuit current contributed from the PV side, which severely reduces the sensitivity or even causes the failure of traditional phase selection methods based on current variation.
To address this issue, this paper proposes a novel fault phase selection method based on the local phase-to-phase voltage difference variation combined with zero-sequence voltage at the protection installation point. The system voltage is primarily dominated by the strong system-side source and is relatively less affected by the weak-infeed PV plant. During fault transients, it can exhibit clearer and more robust asymmetry characteristics, thus providing a new criterion basis for reliable phase selection. The method is logically straightforward and is detailed as follows.
First, the presence of a ground fault is distinguished by detecting the magnitude of the zero-sequence voltage
(a) If (
(b) If (
(c) If (
If none of the above conditions are met, a double-phase-to-ground fault is determined. Then, based on the maximum value among the three phase-to-phase voltage difference variations:
(d) If (
(e) If (
(f) If (
For a non-ground fault, the phase-to-phase short-circuit type is identified according to the following rules:
(g) If (
(h) If (
(i) If (
In the above criteria, the setting coefficients m1 and m2 are set to 1.5 and 4, respectively. This method relies solely on local voltage quantities, effectively overcoming the influence of PV-side current weak-infeed characteristics, and provides adaptive and reliable fault type information for subsequent protection and control stages.
The robustness of the proposed phase selection method based on voltage variations is systematically analyzed from three aspects: measurement noise interference, the grid disturbances, and operating conditions with different transition resistances.
In the presence of measurement noise, the criterion for single-phase-to-ground faults is applied to select fault phases through amplitude comparison between voltage variations of sound phases and voltage differences of sound-faulty phase pairs. Small and irregular random voltage fluctuations are produced by noise in each phase. The core voltage characteristics are not changed, and the relative amplitude relationship is not damaged either. The criterion for phase-to-phase faults is adopted to identify faults through amplitude comparison between the voltage variation of the sound phase and those of the two faulty phases. Fault characteristics that voltage variations of faulty phases are much larger than those of the sound phase are not fabricated by noise. Only small and irregular disturbances are introduced, and the amplitude comparison logic of the criteria is not affected. Misjudgments caused by noise are avoided for both criteria, and favorable robustness is obtained.
Under the grid disturbances, synchronous small-amplitude fluctuations of three-phase voltages are caused. The phase-to-phase voltage difference characteristics required by single-phase-to-ground fault criteria are not formed, so the operation conditions of the criterion are not satisfied. The characteristic that voltage variations of faulty phases are obviously larger than those of the sound phase required by phase-to-phase fault criteria is not presented, so the criterion is not activated. Thus, misoperation caused by grid disturbances is effectively avoided for both phase selection criteria.
Under conditions with different transition resistances, the voltage of the faulty phase drops greatly in single-phase-to-ground faults with low transition resistance, and the corresponding phase-to-phase voltage difference is quite distinct. The amplitude of voltage variations is reduced in faults with high transition resistance, but the relative phase-to-phase voltage difference is still identified effectively. The sensitivity of the criterion is reduced only in faults with extremely high transition resistance due to the loss of voltage characteristics. In phase-to-phase faults with low transition resistance, the voltage of faulty phases drops significantly, and the gap of voltage variations between faulty phases and the sound phase is clearly distinguished. The amplitude gap is narrowed in faults with high transition resistance but still meets the requirement of identification. The criterion fails only in faults with extremely high transition resistance because of indistinct voltage characteristics. Such a limitation is shared by all phase selection methods based on voltage characteristics.
Simulation studies in Section 5 will verify the effectiveness and robustness of the proposed phase selection approach under the typical grid disturbance of load switching and high transition resistance.
(3) Activate the Enhanced IBR Control Strategy
Following protection startup and fault phase selection, the enhanced IBR control strategy described in Section 3 is activated. First, the protection device captures the voltage and current data at the point of common coupling before and after the fault, extracting the positive-sequence fault components
The switching process follows the conventional low-voltage ride-through control framework: the outer-loop controllers (e.g., DC voltage control and reactive power control) are first blocked, and the positive-sequence current references for the inner current loop are switched to
To ensure a smooth control mode transition and maintain inverter stability during the fault transient, a gradual reference transition scheme is employed. Specifically, the calculated current references are passed through a first-order low-pass filter before being fed into the current inner loop, thereby mitigating current surges and oscillations that may arise from abrupt reference changes. The filter time constant is selected as 1–2 ms, which provides sufficient dynamic response while effectively attenuating high-frequency noise. In addition, the PI controllers in the current loop are equipped with anti-windup protection to prevent overshoot and oscillations caused by integrator saturation during reference variations. Furthermore, all current references are strictly limited to the inverter’s maximum allowable current
It is worth noting that the control structure remains unchanged before and after the switching process—both are based on vector control in the synchronous reference frame—and only the reference calculation method is altered. Consequently, the stability of the control loop is inherently maintained. The entire switching process is completed within 2–3 power frequency cycles, which is compatible with the fault discrimination timeframe of the protection element and does not compromise its speed. The above mechanism ensures a smooth and fast switching process, and its dynamic response characteristics, as well as control stability under various fault scenarios, will be demonstrated in the subsequent simulation analysis.
(4) Apply Protection Criterion
With
To verify the effectiveness and reliability of the proposed protection scheme, a simulation model is established in PSCAD/EMTDC based on Fig. 1, with detailed parameters listed in Table 2. The verification in this section is organized as follows: first, the effectiveness of the proposed control strategy and the correctness of the fault phase selection method are tested (Section 5.1); then, the performance of the proposed protection criterion under different fault conditions is fully evaluated (Section 5.2).

5.1 Verification of the Proposed Control Strategy
The core of the proposed strategy is to enable

Figure 10: Phase of short-circuit current and fault current under conventional control strategy. (a) ABC; (b) AG; (c) BCG; (d) BC.

Figure 11: Phase of short-circuit current and fault current under the control strategy proposed in this paper. (a) ABC; (b) AG; (c) BCG; (d) BC.
As illustrated in Fig. 10, a pronounced angle difference between
In contrast, Fig. 11 illustrates that the angle waveforms of
5.2 Verification of the Single-Ended Protection Principle
To verify the effectiveness of the faulted-phase selection method proposed in this paper, A fault is set 30 km ahead of bus N at t = 2 s, with 45 Ω transition resistance and 1 s duration. Table 3 lists the faulted-phase selection results.

As can be seen from Table 3, when a grounding fault occurs, the simulated zero-sequence voltage components are all significantly non-zero, which satisfies the initial criterion for identifying a grounding fault. Furthermore, by examining the phase-to-phase voltage variation data, it is observed that AG, BG, and CG faults respectively meet the relative magnitude relationships defined in criteria (a), (b), and (c) for the corresponding phase-to-phase voltage variations, thus enabling correct identification of the respective single-phase-to-ground faults. In the case of phase-to-phase-to-ground faults, ABG, BCG, and CAG faults are also accompanied by zero-sequence voltage components, and their maximum phase-to-phase voltage variations align with criteria (d), (e), and (f), respectively. Therefore, the proposed method can accurately distinguish between different types of double-phase-to-ground faults. When phase-to-phase faults occur, the zero-sequence voltage component is zero, leading the system to proceed with the non-grounding fault identification process. Here, the fault data for AB, BC, and CA satisfy criteria (g), (h), and (i), respectively, which describe the characteristic that the voltage variations between two phases are significantly larger than that of the third phase, thereby achieving reliable phase selection for the corresponding phase-to-phase short circuits. In summary, based on the criteria proposed, the simulation data for various fault types strictly trigger the corresponding judgment conditions, and the phase selection results are fully consistent with the preset fault types. This demonstrates that the proposed phase selection method based on phase-to-phase voltage variation exhibits good effectiveness and reliability under the described simulation conditions.
Table 4 shows the quantitative results under load switching disturbance and three typical faults, i.e., A-phase-to-ground (AG), phase-B-phase-C (BC), and phase-B-phase-C-to-ground (BCG). During 1.5–1.52 s after load switching, the PCC voltage remains nearly unchanged as shown in the table, while the inverter current decreases slightly owing to the constant power control of the renewable energy source; meanwhile, the starting signal and phase selection signal both keep 0 under all fault conditions, which indicates that the proposed scheme does not mal-operate under load variation and has strong immunity against load switching disturbance. When a fault occurs at 2.0 s, the PCC voltage drops obviously in Fig. 12 (consistent with the quantitative data in Table 4), the starting signal operates reliably, and the faulty phase selection result is correct, which verifies that the proposed starting and phase selection method not only avoids false operation under non-fault disturbances but also maintains reliable operating performance under various typical faults, fully demonstrating its effectiveness and robustness.


Figure 12: The PCC voltage waveforms under different fault types. (a) AG; (b) BCG; (c) BC.
5.2.2 Protection Performance Verification under Different Fault Scenarios
Building on the verified effectiveness of the control strategy, the operating performance of the protection criterion is further evaluated under different fault scenarios.
(1) Different Fault Locations
To assess the performance at various fault distances, different faults (ABC, BC, BCG) are applied at 10, 35, and 60 km from Bus N (t = 2 s, Rf = 35 Ω). Figs. 13–15 show the angle waveforms of

Figure 13: Current phase and measured reactance at 10 km. (a) ABC; (b) BC; (c) BCG; (d)

Figure 14: Current phase and measured reactance at 35 km. (a) ABC; (b) BC; (c) BCG; (d)

Figure 15: Current phase and measured reactance at 60 km. (a) ABC; (b) BC; (c) BCG; (d)
The simulation results indicate that the fault location directly affects the impedance composition of the fault loop, leading to a monotonic variation in
(2) Different Transition Resistances
Transition resistance is a key factor leading to the performance degradation of distance protection. To verify the tolerance capability of the proposed strategy, AG, BC, BCG, and ABC faults were simulated at a point 45 km from bus N in the forward direction at t = 2 s. The fault duration was 1 s, and IBR capacity was 15 MW. The transition resistance

As summarized in Table 5, the fault current phase exhibits a regular shift with varying transition resistance
(3) Different PV Capacities
To verify the adaptability of the proposed strategy to different IBRs capacities, faults were simulated at a point 30 km from bus N in the forward direction at t = 2 s (

As presented in Table 6, IBRs capacity was varied from 5 to 75 MW, corresponding to an SCR range from approximately 1:20 to 1:1.33, thereby covering low- to high-penetration scenarios.
The simulation results indicate that the phase difference between
(4) Impact of Distribution Capacitance
To validate the impact of distributed capacitance on the proposed scheme in this paper, a comparative simulation is conducted. It is assumed that an AB two-phase grounding fault (ABG), an A-phase grounding fault (AG), and a three-phase short-circuit fault (ABC) occur at a distance of 35 km from bus N at t = 2.0 s, with

As shown in Table 7, under different distributed line capacitance conditions,
(5) Weak-Grid Scenarios
To further evaluate the robustness of the proposed control-protection coordination strategy under weak-grid conditions, supplementary simulations are performed with elevated grid-side equivalent impedance
As shown in Table 8, under both weak-grid configurations, the start-up criterion based on the “OR” logic is reliably triggered. Taking the voltage criterion as an example,

Furthermore, the IBR-side current angle
5.3 Comparison with Existing Methods
To verify the performance of the proposed distance protection scheme, it is compared with the control-protection coordination method in Ref. [27] and the adaptive distance protection method in Ref. [28]. The PV capacity is set to 15 MW unless otherwise stated. Three fault types are employed: AG, BC, and BCG. The simulation scenarios are configured as follows:
Weak-grid condition: The grid-side equivalent impedance is 160 Ω, representing low short-circuit capacity. A fault is placed 45 km from bus N with fault resistance.
High fault-resistance condition: A fault resistance is set at 45 km from bus N to test performance under high-resistance faults.
The protection operation results and analysis are listed in Table 9.

From Table 9, under the weak grid scenario, the operational performance of the three methods shows significant differences: the proposed method achieves 100% reliable operation for three typical faults (AG, BC, and BCG), with tripping times concentrated in 2.02–2.03 s; Ref. [27] operates reliably only for AG and BCG faults but fails to operate for BC phase-to-phase faults, with tripping times of 2.05–2.07 s. The core reason for its failure in BC faults is its reliance on dynamic phase synchronization between the IBR-side and grid-side currents. In weak grids, the fault current amplitude attenuates, and BC phase-to-phase faults lack zero-sequence components to enhance signal characteristics, leading to the loss of phase synchronization accuracy and the additional impedance being unable to maintain a pure resistive characteristic; Ref. [28] operates normally only for AG and BC faults but fails to operate for BCG double-phase-to-ground faults, with tripping times of 2.03–2.07 s. The core reason for its failure in BCG faults is its dependence on negative-sequence components to calculate the additional impedance angle. In weak grids, the grid-side negative-sequence components attenuate significantly, and BCG faults involve the superimposed interference of positive-sequence, negative-sequence and zero-sequence components, resulting in decreased separation accuracy of sequence components and calculation errors exceeding the fault tolerance threshold of the protection criterion. From the perspective of operating speed characteristics, the proposed method has the fastest operating speed and the smallest fluctuation range (only 0.01 s), which is 0.02–0.05 s faster than Ref. [27] and 0.01–0.04 s faster than Ref. [28], fully demonstrating its superior operating sensitivity and rapidity.
Under the high fault resistance scenario, the operational performance of the three methods also shows significant differences: the proposed method achieves 100% reliable operation for three typical faults (AG, BC, and BCG), with tripping times concentrated in 2.03–2.04 s; Ref. [27] operates reliably only for BC and BCG faults but fails to operate for AG faults, with tripping times of 2.09–2.11 s. The core reason for its failure in AG faults is its reliance on dynamic phase synchronization between the IBR-side and grid-side currents. In high fault resistance conditions, the transition resistance greatly suppresses the fault current and results in a sharp attenuation of the fault current amplitude. Meanwhile, the zero-sequence components for AG faults are further weakened, leading to insufficient signal characteristics for phase synchronization and a serious decline in synchronization accuracy. Therefore, the additional impedance cannot maintain a pure resistive characteristic, which results in protection failure; Ref. [28] operates normally only for AG and BC faults but fails to operate for BCG faults, with tripping times of 2.03–2.07 s. The core reason for its failure in BCG faults is its dependence on negative-sequence components to calculate the additional impedance angle. In high fault resistance conditions, the grid-side negative-sequence components attenuate further, and BCG faults involve the superimposed interference of positive-sequence, negative-sequence and zero-sequence components, leading to a significant decrease in the separation accuracy of sequence components and calculation errors exceeding the fault tolerance threshold of the protection criterion. From the perspective of operating speed characteristics, the proposed method has the fastest operating speed and the smallest fluctuation range (only 0.01 s), which is 0.05–0.08 s faster than Ref. [27] and 0.01–0.04 s faster than Ref. [28], fully demonstrating its superior operating sensitivity and rapidity. Meanwhile, reliable operation under all fault types indirectly reflects its superiority in error margin control.
In summary, the proposed method eliminates the inherent reliance of traditional schemes on phase synchronization and negative-sequence component extraction in principle. It realizes the innovative reconstruction of the protection mechanism, effectively overcomes the failure-to-operate bottleneck of the compared methods under specific fault conditions, and greatly extends the applicable range of relay protection strategies. Its tripping time is stably controlled within 2.02–2.04 s, with fast response and extremely low timing fluctuation, demonstrating superior operating rapidity and stability. In terms of fault identification, the proposed method operates reliably under all fault types, provides higher discrimination accuracy and protection sensitivity, and ensures excellent operating selectivity. Meanwhile, it maintains stable performance under extreme conditions such as weak grid and high-impedance faults, is rarely affected by changes in grid operating states and fault characteristics, and fully presents outstanding multi-scenario adaptability and robustness.
To address the inadaptability of conventional distance protection to IBR-connected lines, a novel control-protection coordination strategy is proposed. Improving the current references of IBRs’ inverter control, a single-ended protection principle immune to the additional impedance is developed based on the measured fault distance. The main findings obtained through simulation tests are as follows.
(1) Under the derived current references of IBRs’ inverter control, the current angle on the IBR side of the protected line equals that at the fault point, and the angle error between them is within 1°. This condition effectively ensures that the additional impedance angle remains constant, independent of IBR control strategies and fault resistance. The current references are determined solely by the electrical quantities
(2) The proposed protection principle can effectively identify various types of faults occurring at different locations along the protected line. Under the condition that the transition resistance is up to 100 Ω and the IBR capacity ratio is 1:1.33, the protection can still operate correctly and reliably. The proposed protection criterion utilizes only the voltage and current at the relay location, does not require any electrical quantities from the remote end of the protected line, and is both communication-independent and easy to implement.
(3) Although it is verified through simulations that the proposed control-protection coordinated strategy can effectively mitigate the influence of additional impedance on the measured fault distance, hardware-in-the-loop (HIL) testing is still required for future research. Meanwhile, when additional loads or other power sources are connected to the IBR side of the protected line, the effectiveness of the proposed strategy requires further verification.
Acknowledgement: Not applicable.
Funding Statement: The study is supported by the National Natural Science Foundation of China (Grant No. 52107069).
Author Contributions: The authors confirm contribution to the paper as follows: Sumei Liu: conceptualization, supervision, review & editing; Jizeng Wu: methodology, formal analysis, validation, writing—original draft; Yinghong Zhang: investigation, resources; Ran Zheng: review & editing. All authors reviewed and approved the final version of the manuscript.
Availability of Data and Materials: The data confirm that data in this study are available on request.
Ethics Approval: Not applicable.
Conflicts of Interest: The authors declare no conflicts of interest.
References
1. Gu Y, Green TC. Power system stability with a high penetration of inverter-based resources. Proc IEEE. 2023;111(7):832–53. doi:10.1109/jproc.2022.3179826. [Google Scholar] [CrossRef]
2. Liang Y, Li W, Lu Z. Effect of inverter-interfaced renewable energy power plants on negative-sequence directional relays and a solution. IEEE Trans Power Deliv. 2021;36(2):554–65. doi:10.1109/TPWRD.2020.2984653. [Google Scholar] [CrossRef]
3. Huynh H, Khatiwada A, Poudel B, Amiri E, Quinteros MI, Field TE, et al. Experimental analysis of transmission line protection functions in grid-connected IBR. IEEE Trans Ind Appl. 2025;61(2):2300–12. doi:10.1109/TIA.2024.3522222. [Google Scholar] [CrossRef]
4. Jia K, Li B, Bi T. Impact of wind power integration on directional elements of transmission line distance protection. Autom Electr Power Syst. 2014;38(23):100–6. (In Chinese). doi:10.1109/apap.2011.6180418. [Google Scholar] [CrossRef]
5. Zheng T, Liu H, Bi T. Mechanism analysis and countermeasures for maloperation of distance protection for outgoing lines from renewable power stations. Proc CSEE. 2020;40(11):3493–504. (In Chinese). [Google Scholar]
6. George N, Naidu OD, Pradhan AK. Distance protection for lines connecting converter interfaced renewable power plants: adaptive to grid-end structural changes. IEEE Trans Power Deliv. 2023;38(3):2011–21. doi:10.1109/TPWRD.2022.3231403. [Google Scholar] [CrossRef]
7. Jalilian A, Muttaqi KM, Sutanto D, Robinson DA. Distance protection of transmission lines in presence of inverter-based resources: a new earth fault detection scheme during asymmetrical power swings. IEEE Trans Ind Appl. 2022;58(2):1899–909. doi:10.1109/TIA.2022.3146219. [Google Scholar] [CrossRef]
8. Koloushani SM, Taher SA. Enhancing distance protection in transmission grids with high penetration of renewable energy sources through cooperative protection. IET Gener Trans Dist. 2024;18(21):3462–75. doi:10.1049/gtd2.13295. [Google Scholar] [CrossRef]
9. Yan H, Deng H, Zheng J. An adaptive distance protection strategy for distribution networks with inverter-based distributed generation. J Electr Eng Technol. 2026;21(1):233–50. doi:10.1007/s42835-025-02449-2. [Google Scholar] [CrossRef]
10. Liang Y, Li W, Zha W. Adaptive mho characteristic-based distance protection for lines emanating from photovoltaic power plants under unbalanced faults. IEEE Syst J. 2021;15(3):3506–16. doi:10.1109/JSYST.2020.3015225. [Google Scholar] [CrossRef]
11. Mishra P, Pradhan AK, Bajpai P. Adaptive distance relaying for distribution lines connecting inverter-interfaced solar PV plant. IEEE Trans Ind Electron. 2021;68(3):2300–9. doi:10.1109/TIE.2020.2975462. [Google Scholar] [CrossRef]
12. Xie Y, Zou X, Duan M, Fan F, Wang H, Liu Y. Distance protection for lines terminated by inverter-based resources compatible with various inverter control schemes. IEEE Trans Ind Electron. 2025;72(12):13151–63. doi:10.1109/TIE.2025.3577310. [Google Scholar] [CrossRef]
13. Banaiemoqadam A, Hooshyar A, Azzouz MA. A control-based solution for distance protection of lines connected to converter-interfaced sources during asymmetrical faults. IEEE Trans Power Deliv. 2020;35(3):1455–66. doi:10.1109/TPWRD.2019.2946757. [Google Scholar] [CrossRef]
14. Daryabar H, Abedini M, Davarpanah M. An adaptive K-factor control scheme for inverter-based resources to enhance operation of distance protection. Int J Electr Power Energy Syst. 2025;173(4):111349. doi:10.1016/j.ijepes.2025.111349. [Google Scholar] [CrossRef]
15. Zhou Z, Yu S, Li Y, Wang X, Liu H. Analysis on incorrect operation mechanism of phase-comparison distance protection caused by power angle variation in new energy transmission via VSC-HVDC. Proc CSEE. 2023;43(5):1730–9. (In Chinese). doi:10.13334/j.0258-8013.pcsee.222160. [Google Scholar] [CrossRef]
16. Paladhi S, Pradhan AK. Adaptive distance protection for lines connecting converter-interfaced renewable plants. IEEE J Emerg Sel Top Power Electron. 2021;9(6):7088–98. doi:10.1109/jestpe.2020.3000276. [Google Scholar] [CrossRef]
17. Chao C, Zheng X, Weng Y, Liu Y, Gao P, Tai N. Adaptive distance protection based on the analytical model of additional impedance for inverter-interfaced renewable power plants during asymmetrical faults. IEEE Trans Power Deliv. 2022;37(5):3823–34. doi:10.1109/TPWRD.2021.3138128. [Google Scholar] [CrossRef]
18. Xie Z, Li B, He J, Shao M, Zhou B, Wu T, et al. Error analysis and improved method of time-domain distance protection for wind power transmission lines. Int J Electr Power Energy Syst. 2024;160(4):110081. doi:10.1016/j.ijepes.2024.110081. [Google Scholar] [CrossRef]
19. Abdelemam AM, Zeineldin H, Al-Durra A, El-Saadany EF. A positive/negative voltage sequence droop-based differential protection scheme for islanded microgrids with inverter-based DG. IEEE Trans Ind Inform. 2025;21(1):327–36. doi:10.1109/TII.2024.3452209. [Google Scholar] [CrossRef]
20. Xue L, Mu L, Fang C, Zhu J. Research on active protection method for microgrids based on harmonic injection. IEEE Trans Smart Grid. 2025;16(1):209–22. doi:10.1109/TSG.2024.3453369. [Google Scholar] [CrossRef]
21. Yu H, Lu Z, Liu Y, Gao Y, Wan J. Injected harmonic feature based protection scheme for active distribution networks with high proportion IIDGs. IEEE Access. 2024;12:35282–99. doi:10.1109/access.2024.3368890. [Google Scholar] [CrossRef]
22. Zheng T, Lv W, Zhuang X, Ma J. Improved time-domain distance protection for asymmetrical faults based on adaptive control of MMC in offshore AC network. Int J Electr Power Energy Syst. 2023;152(1):109229. doi:10.1016/j.ijepes.2023.109229. [Google Scholar] [CrossRef]
23. Zheng T, Zhang R, Lv W, Liu S. Improved time-domain distance protection based on fault active control for long transmission lines of PV/BES hybrid power generation system. Int J Electr Power Energy Syst. 2024;159(6–7):110049. doi:10.1016/j.ijepes.2024.110049. [Google Scholar] [CrossRef]
24. Naidu OD, George N, Zubic S, Krakowski M. Time-domain-based distance protection for transmission networks: secure and reliable solution for complex networks. IEEE Access. 2023;11(1):104656–75. doi:10.1109/ACCESS.2023.3316115. [Google Scholar] [CrossRef]
25. Chao C, Zheng X, Weng Y, Liu Z, Ye H, Liu H, et al. Collaborative solution of distance protection and dual current control for outgoing lines of inverter-based resources during line-to-line faults. IEEE Trans Smart Grid. 2024;15(4):3782–94. doi:10.1109/TSG.2024.3369767. [Google Scholar] [CrossRef]
26. Miao Z, Zhou Y, Fan L, Wang Z. An alternative control structure for grid-following converters of inverter-based resources. IEEE Open Access J Power Energy. 2023;10:283–93. doi:10.1109/OAJPE.2023.3250668. [Google Scholar] [CrossRef]
27. Ji L, Zhang LN, Jiang EY, Hong QT, Mi Y, Fu Y. Research on new energy active fault control to improve adaptability of distance protection. Acta Energiae Solaris Sin. 2022;43(7):22–9. (In Chinese). doi:10.19912/j.0254-0096.tynxb.2020-1245. [Google Scholar] [CrossRef]
28. Yang G, Wang R, Wang C, Yu Y, Lu P. Principle of distance protection for new energy transmission lines based on the characteristics of negative sequence suppression strategy. Power Syst Technol. 2025. (In Chinese). [Google Scholar]