Open Access
ARTICLE
Optimum Operation of Low-Voltage AC/DC Distribution Areas with Embedded DC Interconnections under Three-Phase Unbalanced Compensation Conditions
Zhukui Tan1, Dacheng Zhou1, Song Deng1, Jikai Li2,*, Zhuang Wu2, Qihui Feng1, Xuan Zhang1
1 Electric Power Research Institute of Guizhou Power Grid Co., Ltd., Guiyang, 550002, China
2 XJ Electric Co., Ltd., Xuchang, 461000, China
* Corresponding Author: Jikai Li. Email:
(This article belongs to the Special Issue: Construction and Control Technologies of Renewable Power Systems Based on Grid-Forming Energy Storage)
Energy Engineering https://doi.org/10.32604/ee.2025.069610
Received 26 June 2025; Accepted 06 August 2025; Published online 29 August 2025
Abstract
This paper presents an optimal operation method for embedded DC interconnections based on low-voltage AC/DC distribution areas (EDC-LVDA) under three-phase unbalanced compensation conditions. It can optimally determine the transmission power of the DC and AC paths to simultaneously improve voltage quality and reduce losses. First, considering the embedded interconnected, unbalanced power structure of the distribution area, a power flow calculation method for EDC-LVDA that accounts for three-phase unbalanced compensation is introduced. This method accurately describes the power flow distribution characteristics under both AC and DC power allocation scenarios. Second, an optimization scheduling model for EDC-LVDA under three-phase unbalanced conditions is developed, incorporating network losses, voltage quality, DC link losses, and unbalance levels. The proposed model employs an improved particle swarm optimization (IPSO) two-layer algorithm to autonomously select different power allocation coefficients for the DC link and AC section under various operating conditions. This enables embedded economic optimization scheduling while maintaining compensation for unbalanced conditions. Finally, a case study based on the IEEE 13-node system for EDC-LVDA is conducted and tested. The results show that the proposed optimal operation method achieves a 100% voltage compliance rate and reduces network losses by 13.8%, while ensuring three-phase power balance compensation. This provides a practical solution for the modernization and upgrading of low-voltage power grids.
Keywords
Power loss optimization; low-voltage AC/DC distribution areas; embedded DC interconnections